SOLENOID OPERATED GAS SAFETY SHUT-OFF VALVES

GAS SAFE REGISTER TM1
Normally Closed without Manual Reset

Closed by power interruption in less than one second. Automatic reset so that electrical power alone will re-open them in less than one second. With tappings suitable for CPI switch (see page 19 of our main catalogue), pressure gauge, or connection to proving and interlock systems. They can be electrically connected to an alarm system and/or to a knock-off switch. These valves are manufactured to Class A in accordance with BS EN 161 : 2002, and to 90/396/EEC - 73/23/EEC - 89/336/EEC. Certificate CE EC - 87/07/009. Valves are protected to IP 54 which has coil protection to IP 65. Incorporate AISI 303 steel mesh filter. Voltage 230 V AC (+10 % -15 %), 50 - 60 Hz. Coil insulation to Class F. Ambient temperature : -15°C to 60°C. Flow rate diagram available on request. Mount directly in pipeline not more than 90° from vertical axis.
For Natural Gas, LPG and Air.

Flange Size: PN16. Nominal Bore: 65 mm. Max. inlet pressure: 200 mbar.
Consumption: 18VA
Overall Dimensions: A: 310 mm. B: 343 mm. C: 200 mm. D: 148 mm
Weight: 15 kg.
Part No.DescriptionUnit PriceQty


Flange Size: PN16. Nominal Bore: 80 mm. Max. inlet pressure: 200 mbar.
Consumption: 18VA
Overall Dimensions: A: 310 mm. B: 343 mm. C: 200 mm. D: 148 mm
Weight: 15 kg.
Part No.DescriptionUnit PriceQty


Flange Size: PN16. Nominal Bore: 100 mm. Max. inlet pressure: 200 mbar.
Consumption: 18VA
Overall Dimensions: A: 350 mm. B: 384 mm. C: 250 mm. D: 185 mm
Weight: 37 kg.
Part No.DescriptionUnit PriceQty


Flange Size: PN16. Nominal Bore: 125 mm. Max. inlet pressure: 200 mbar.
Consumption: 290VA
Overall Dimensions: A: 400 mm. B: 592 mm. C: 300 mm. D: 250 mm
Part No.DescriptionUnit PriceQty


Flange Size: PN16. Nominal Bore: 150 mm. Max. inlet pressure: 200 mbar.
Consumption: 290VA
Overall Dimensions: A: 480 mm. B: 630 mm. C: 300 mm. D: 250 mm
Part No.DescriptionUnit PriceQty

Normally Closed with Manual Reset

Details as above, but they have to be manually reset. Electrical power alone will not re-open them (they have to be manually re-opened in the presence of current). This is a safety feature.
Voltage 240 V AC. The valve may be mounted horizontally or vertically, but not upside down.
For natural Gas, LPG and Air.

Thread Size: 1/2" BSP. Nominal Bore: 15 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 72 mm. B: 150 mm. C: 52 mm. D: 85 mm.
* Reset by pressing a button, not as illustrated.
Part No.DescriptionUnit PriceQty



Thread Size: 3/4" BSP. Nominal Bore: 20 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 86 mm. B: 160 mm. C: 70 mm. D: 85 mm.
* Reset by pressing a button, not as illustrated.
Part No.DescriptionUnit PriceQty



Thread Size: 1" BSP. Nominal Bore: 25 mm. Max. inlet pressure: 500 mbar.
* Reset by pressing a button, not as illustrated.
Part No.DescriptionUnit PriceQty



Thread Size: 1.1/4" BSP. Nominal Bore: 32 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 150 mm. B: 221 mm. C: 110 mm. D: 85 mm.
Part No.DescriptionUnit PriceQty


Thread Size: 1.1/2" BSP. Nominal Bore: 40 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 150 mm. B: 221 mm. C: 110 mm. D: 85 mm.
Part No.DescriptionUnit PriceQty


Thread Size: 2" BSP. Nominal Bore: 50 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 170 mm. B: 285 mm. C: 135 mm. D: 120 mm.
Part No.DescriptionUnit PriceQty



Flange Size: 65mm. Nominal Bore: 65 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 310 mm. B: 360 mm. C: 200 mm. D: 120 mm.
Part No.DescriptionUnit PriceQty



Flange Size: 80mm. Nominal Bore: 80 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 310 mm. B: 360 mm. C: 200 mm. D: 120 mm.
Part No.DescriptionUnit PriceQty


Flange Size: 100mm. Nominal Bore: 100 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 350 mm. B: 360 mm. C: 200 mm. D: 120 mm.
Part No.DescriptionUnit PriceQty