Gas Meter Connectors & Fittings GAS SAFE REGISTER TM

SOLENOID OPERATED GAS SAFETY SHUT-OFF VALVES

Normally Closed without Manual Reset


Closed by power interruption in less than one second. Automatic reset so that that electrical power alone will re-open them. They can be electrically connected to an alarm system and/or to a knock-off switch. These valves are manufactured to Class A in accordance with EN 161 and DIN 3391-3394 standards. Valves are protected to IP 54. Integral strainer fitted to size.
1.1/4" to 3" inclusive, plus the 65 mm and 80 mm sizes. Voltage 240 V AC. Coil insulation to Class F. Ambient temperature: -15 °C to 60 °C. Flow rate diagram available on request. The valve may be mounted horizontally or vertically, but not upside down.
For Natural Gas, LPG and Air.

Thread Size: 1/4" BSP. Nominal Bore: 8 mm. Max. inlet pressure: 500 mbar.
Consumption: 9 W.
Overall Dimensions: A: 40.5 mm. B: 83 mm. C: 42 mm.
Weight: 0.28 kg.
Part No.Description Unit PriceQty


Thread Size: 3/8" BSP. Nominal Bore: 10 mm. Max. inlet pressure: 350 mbar.
Consumption: 12 W.
Overall Dimensions: A: 72 mm. B: 112 mm. C: 52 mm. D: 85 mm
Weight: 0.43 kg.
Part No.Description Unit PriceQty


Thread Size: 1/2" BSP. Nominal Bore: 15 mm. Max. inlet pressure: 350 mbar.
Consumption: 20VA
Overall Dimensions: A: 72 mm. B: 112 mm. C: 52 mm. D: 85 mm
Weight: 1.16 kg.
Part No.Description Unit PriceQty


Thread Size: 3/4" BSP. Nominal Bore: 20 mm. Max. inlet pressure: 200 mbar.
Consumption: 25VA
Overall Dimensions: A: 86 mm. B: 156 mm. C: 70 mm. D: 96 mm
Weight: 2.03 kg.
Part No.Description Unit PriceQty


Thread Size: 1" BSP. Nominal Bore: 25 mm. Max. inlet pressure: 200 mbar.
Consumption: 25VA
Overall Dimensions: A: 100 mm. B: 156 mm. C: 75 mm. D: 96 mm
Weight: 1.8 kg.
Part No.Description Unit PriceQty


Thread Size: 1.1/4" BSP. Nominal Bore: 32 mm. Max. inlet pressure: 200 mbar.
Consumption: 50VA
Overall Dimensions: A: 150 mm. B: 214 mm. C: 110 mm. D: 118 mm
Weight: 5.6 kg.
Part No.Description Unit PriceQty


Thread Size: 1.1/2" BSP. Nominal Bore: 40 mm. Max. inlet pressure: 200 mbar.
Consumption: 50VA
Overall Dimensions: A: 150 mm. B: 214 mm. C: 110 mm. D: 118 mm
Weight: 5.6 kg.
Part No.Description Unit PriceQty


Thread Size: 2" BSP. Nominal Bore: 50 mm. Max. inlet pressure: 200 mbar.
Consumption: 50VA
Overall Dimensions: A: 170 mm. B: 220 mm. C: 135 mm. D: 123 mm
Weight: 6.1 kg.
Part No.Description Unit PriceQty


Thread Size: 2.1/2" BSP. Nominal Bore: 65 mm. Max. inlet pressure: 200 mbar.
Consumption: 68VA
Overall Dimensions: A: 220 mm. B: 290 mm. C: 170 mm. D: 145 mm
Weight: 13 kg.
Part No.Description Unit PriceQty


Thread Size: 3" BSP. Nominal Bore: 65 mm. Max. inlet pressure: 200 mbar.
Consumption: 68VA
Overall Dimensions: A: 220 mm. B: 290 mm. C: 170 mm. D: 145 mm
Weight: 18 kg.
Part No.Description Unit PriceQty


Flange Size: 65mm. Nominal Bore: 65 mm. Max. inlet pressure: 200 mbar.
Consumption: 18VA
Overall Dimensions: A: 310 mm. B: 343 mm. C: 200 mm. D: 148 mm
Weight: 15 kg.
Part No.Description Unit PriceQty


Flange Size: 80mm. Nominal Bore: 80 mm. Max. inlet pressure: 200 mbar.
Consumption: 18VA
Overall Dimensions: A: 310 mm. B: 343 mm. C: 200 mm. D: 148 mm
Weight: 15 kg.
Part No.Description Unit PriceQty


Flange Size: 100mm. Nominal Bore: 100 mm. Max. inlet pressure: 200 mbar.
Consumption: 18VA
Overall Dimensions: A: 350 mm. B: 384 mm. C: 250 mm. D: 185 mm
Weight: 37 kg.
Part No.Description Unit PriceQty


Closed Position Indicators for Valves without Manual Reset

The closed position indicator switch is a mechanically activated microswitch for monitoring the position of the above ‘Normally closed without manual reset' gas safety shut-off valves.
To be fitted into the bottom of the valve body, this may be used for remote monitoring and is suitable for building management systems applications.
SPECIFICATIONS :
Operational voltage : 3 A @ 250
Ambient temperature : -15°C to +60°C
Enclosure : IP 65
Part No.Description Unit PriceQty

Normally Closed with Manual Reset

Details as above, but they have to be manually reset. Electrical power alone will not re-open them (they have to be manually re-opened in the presence of current). This is a safety feature.
Voltage 240 V AC. The valve may be mounted horizontally or vertically, but not upside down.
For natural Gas, LPG and Air.

Thread Size: 1/2" BSP. Nominal Bore: 15 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 72 mm. B: 150 mm. C: 52 mm. D: 85 mm.
* Reset by pressing a button, not as illustrated.
Part No.Description Unit PriceQty



Thread Size: 3/4" BSP. Nominal Bore: 20 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 86 mm. B: 160 mm. C: 70 mm. D: 85 mm.
* Reset by pressing a button, not as illustrated.
Part No.Description Unit PriceQty



Thread Size: 1" BSP. Nominal Bore: 25 mm. Max. inlet pressure: 500 mbar.
* Reset by pressing a button, not as illustrated.
Part No.Description Unit PriceQty



Thread Size: 1.1/4" BSP. Nominal Bore: 32 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 150 mm. B: 221 mm. C: 110 mm. D: 85 mm.
Part No.Description Unit PriceQty


Thread Size: 1.1/2" BSP. Nominal Bore: 40 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 150 mm. B: 221 mm. C: 110 mm. D: 85 mm.
Part No.Description Unit PriceQty


Thread Size: 2" BSP. Nominal Bore: 50 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 170 mm. B: 285 mm. C: 135 mm. D: 120 mm.
Part No.Description Unit PriceQty



Flange Size: 65mm. Nominal Bore: 65 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 310 mm. B: 360 mm. C: 200 mm. D: 120 mm.
Part No.Description Unit PriceQty



Flange Size: 80mm. Nominal Bore: 80 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 310 mm. B: 360 mm. C: 200 mm. D: 120 mm.
Part No.Description Unit PriceQty


Flange Size: 100mm. Nominal Bore: 100 mm. Max. inlet pressure: 500 mbar.
Overall Dimensions: A: 350 mm. B: 360 mm. C: 200 mm. D: 120 mm.
Part No.Description Unit PriceQty




230 V AC KNOCK-OFF SWITCH

Emergency electrical knock-off button. Striking the red knob cuts the electrical supply.
Rotating the knob clockwise a small amount resets the switch. With P/N 13559 the knob is locked when struck, and then can only be released with a key.

Protected to IP 40. 230 V AC 10(6) Amps.
The switch used conforms to EN 60947-5-1.
Part No.Description Unit PriceQty

Part No.Description Unit PriceQty



ELECTRO-THERMAL LINK

The electro-thermal link is for installing in a position where a fire hazard may occur, e.g.
above a burner of an air heater or boiler. The fire will melt the fusible metal link and interrupt the electrical supply to either a gas valve or alarm etc. The link consists of a purpose built steel box with a perforated cover having a temperature sensitive fuse. The unit should be mounted so that the perforated cover faces downwards and ventilation holes in the sides must not be obstructed.

TECHNICAL SPECIFICATION :
The link is electrically rated at 5 amps maximum on 200/250 V, single phase, 50 Hz and melts at 155 °F (68°C). Dimensions : 75 mm length x 50 mm width x 30 mm depth complete with 20 mm conduit entry in one end.

Part No.Description Unit PriceQty



PROVENGAS AUTOMATIC PROVING SYSTEM

An automated means of proving the integrity of a gas installation on a regular and routine basis. Comprises a control panel and isolating unit. Gas solenoid valve needs to be purchased in addition. BG Technology certified.

Part No.Description Unit PriceQty



THERMAL FUSE

The POWER LINK operates as a thermal fuse, through which the controlled circuit is connected. The fuse does not reset when the temperature falls. Cast iron case with perforated steel front cover. Screws directly on to a suitable M20 x 1.5 conduit fitting or pipe (not plastic) 0.3 to 1 metre above possible fire source.

Electrical rating : 230 V - 15 A max.
Fuse rating :       open circuit at ambient temperatures above 72 °C (162 °F), non-resetting.
Part No.Description Unit PriceQty